PropertyTest MethodValue
Hot Surface PerformanceASTM C411Up to 850°F (454°C)
Maximum thickness 6" (152 mm)
Up to 650°F (343°C)
Maximum thickness 8" (203 mm)
Compressive Strength
at 10% Deformation
at 20% Deformation
ASTM C165
90 lb/ft2 (4309 Pa)
130 lb/ft2 (6225 Pa)
Nominal DensityASTM C3033.0 pcf (48 kg/m3)
Water Vapor SorptionASTM C1104< 2.0% by weight, at 120°F (49°C), 95% R.H.
Shot ContentASTM C1335Negligible
Composite Surface Burning Characteristics
Flame Spread
Smoke Developed
9
UL 723, ASTM E84 or CAN/ULC-S102
25
50

Standards Codes Compliance

  • ASTM C612, Mineral Fiber Block & Board Thermal Insulation, Types IA, IB, II
  • ASTM C795, Thermal Insulation for Use Over Austenitic Stainless Steel7
  • Nuclear Regulatory Commission Guide 1.36, Non-Metallic Thermal Insulation7
  • U.S. Coast Guard Approval No. 164.109, Noncombustible Materials
  • CAN/CGSB-51.10–Type 1, Class 1

1. Limited to single layer applications above 650°F (343°C), but not greater than 6" (152mm) thickness.

2. With heat up schedule.

3. The surface burning characteristics of these products have been determined in accordance with UL 723, ASTM E84 or CAN/ULC-S102. Values are reported to the nearest 5 rating.

4. Preproduction qualification testing

5. All values are approximate.

6. The surface burning characteristics of these products have been determined in accordance with ASTM E84, UL 723, and CAN/ULC-S102. These standards should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment, which takes into account all of the factors, which are pertinent to an assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating.

7. Preproduction qualification testing complete and on file. Chemical analysis of each production lot required for total conformance.

8. Available in fire-rated (FR) versions. Visit www.owenscorning.com for product specification data sheets applicable to these products.

9. The surface burning characteristics of these products have been determined in accordance with UL 723, ASTM E84 or CAN/ULC-S102. This standard should be used to measure and describe the properties of materials, products or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use. Values are reported to the nearest 5 rating.